SMARTEN POWER SYSTEMS PVT LIMITED | |
PRODUCT SPECIFICATION | |
DOC REF NO. | RD/SUP/2500/24V/R.01 |
DATE | 14-10-2020 |
PRODUCT FG CODE | |
Product Specification Range of MPPT Solar PCU. | SUPERB 2500VA |
Mains Input mode | |
Mains AC low cut UPS mode | 175VAC ± 10VAC |
Mains AC low cut recovery UPS mode | 185VAC ± 10VAC |
Mains AC high cut UPS mode | 265VAC ± 10VAC |
Mains AC high cut recovery UPS mode | 255VAC ± 10VAC |
Mains AC low cut WUPS mode | 90VAC ± 10VAC |
Mains AC low cut recovery W.UPS mode | 110VAC ± 10VAC |
Mains AC high cut WUPS mode | 295VAC ± 10VAC |
Mains AC high cut recovery W.UPS mode | 285VAC ± 10VAC |
Input Frequency Range | 40Hz to 60Hz |
Voltage Output in Mains Mode | Same as input |
Frequency Output in Mains Mode | Same as input |
Battery | |
Battery Type | LA / Tubular / SMF |
DC input voltage | 24V |
Battery Quantity 12V 100Ah to 220Ah | 2 |
Float charging voltage | 27.4V±0.2V |
Boost charging voltage for LA Battery | 28V±0.3V |
Boost charging voltage for Tubular and SMF Battery | 28.8V±0.3V |
Bulk Absorption Battery Voltage | 29.6±0.2V |
Battery deep Discharge Recovery | Yes (Independent Charger to Recover Deep Discharge Battery) |
Mains Charging Current Enable/Disable | Yes Provide by Keypad |
Charging Current By Grid | 15A±3A |
Backup Mode | |
Output voltage | 220VAC±10% |
Output frequency | 50Hz ± 0.2 Hz |
Output waveform | Pure Sine Wave ≤ 5% THD |
No Load current | <1.5A |
Capacity | 2500VA |
Discharging current @ full load | 70A ± 2A |
Low Battery Warning | 21.2V±0.2V |
Low Battery Cut | 20.8V±0.2V |
Change over time UPS mode | < 10msec |
Change over time WUPS mode | < 25msec |
Switching Element | MOSFET |
Cooling | Temp. Controlled Fan |
Protections | |
Overload in backup mode | Yes provided, system will indicate on display at 101% load |
Short Circuit in Backup Mode | System will shutdown after 3 - retries in case of output short circuit |
Short Circuit in Mains Mode | Mains MCB will trip |
Back feed | System will shutdown in case of back feed and there is no retry |
Over temperature | Yes provided, if heat sink temperature goes above 100°C System will shut down |
Reverse Battery | DC fuse will blown |
Phase to Phase protection in mains mode | Yes provided by electronic |
Solar Charge Controller | |
Solar Charge Controller type | MPPT |
Max Panel wattage can be connected | 1500WATT |
Maximum PV Voltage | 85±2V |
Maximum Battery current | 50Amp. |
Efficiency | > 93% |
Reverse PV protection | Yes provided, it will also display on LCD panel |
Switches | Menu(Select),up,Down,Esc. |
Reverse current flow to PV | Yes provided |
Sharing of current when PV and Grid Both are available | If PV power is not sufficient enough to charge the battery, system will start sharing battery charging from PV and grid. |
DOD definition(Depth of Discharge) | Mains will be connect when battery voltage reach at defined value of the battery voltage. |
DOD (Depth of Discharge) | 20%- if battery voltage is 25.0v±0.2V |
30%- if battery voltage is 24.0v±0.2V | |
40%- if battery voltage is 23.0v±0.2V | |
50%- if battery voltage is 22.0v±0.2V | |
Display and Alarms | |
LCD Initial Display | Welcome, SMARTEN Website Address, System Capacity, Charging Till 90VAC and Deep Discharge Battery, System Setting, UPS / WUPS mode, I/P range 90-295VAC / 170-265VAC, Battery Type Selected LA / SMF / Tubular, DOD. |
LCD Status Display | Mains ON, Input Voltage, Input Frequency, Battery Voltage, Battery Charging, Battery Charged, Charging Current, Backup Mode, UPS ON, UPS OFF, Battery Voltage, Load %, Output Voltage, Output Frequency, Battery Current, PV Current,PV Voltage. Mains Low Cut, Mains High Cut, Mains Not Available, Mains Frequency Cut |
LCD Fault / Protection Status Display | Mains Fuse Blown / MCB Trip, Short Circuit, Overload, Battery Low, High Temperature, Back feed |
Buzzer | Mains Fuse Blown / MCB Trip, Short Circuit, Overload, Battery Low, High Temperature, Back feed |
Safety | |
HV Test Input to Earth | Leakage current <5mA when 1.5kV applied for 1 min |
HV Test Output to Earth | Leakage current <5mA when 1.5kV applied for 1 min |
IR Test Input to Earth | >5MΏ between @ 500VDC |
IR Test Output to Earth | >5MΏ between @ 500VDC |
Earth Leakage current in Mains mode | < 2.5mA |
Earth Leakage current in Backup mode | < 2.5mA |
Environment | |
Operating Temperature | 0°C to 50°C |
Storage Temperature | 0°C to 50°C |
Operating Relative Humidity | 90% Non-Condensing |
Dimensions | |
Dimensions in mm | 340x230x260 |